Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: ELECTRICAL
Permit Number - T04EL01706
Review Name: ELECTRICAL
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
08/19/2004 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Approved | T04EL01706 DENIED 8/17/04 1. Revise the plans to add a requirement to Provide placards at both service disconnects, denoting the presence of the other. NEC 230.2 (E). 2. Per David Mann, there needs to be a fire wall between a laundry and dwelling. Identify such adjacent walls as firewalls on plans. A Building Inspector will be sent to verify. Take out a building permit for such verification, linked to this permit. |