Review Date Reviewer's Name Type of Review Description Status Comments
07/07/2005 DSTARK1 ZONING REVIEW Stop
09/09/2004 PATRICIA GILBERT ENGINEERING REVIEW Approved
09/09/2004 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved T04EL01696 DENIED 8/23/04

1. Per NEC 630.12, it appears that the overcurrent protection for the 2880VA welder should be 20A, not 30A. Please correct or justify otherwise.
2. Put address on both sheets of plans.
3. Specify conduit size and type.
4. Speficy conductor size and type.