Review Details: ELECTRICAL
Permit Number - T04EL01620
Review Name: ELECTRICAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/09/2004 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Approved | T04EL01620 DENIED 8/9/04 - SUBSEQUENTLY CLARIFIED 1. Locate disconnect to parking garage branch per NEC 225.32 as being at the nearest point of entrance of branch circuit conductors. 2. Unclear how (2) (40) would equal 154.4 watts on lighting fixture shcedule. Please clarfiy. 3. Clarify corrosion protection of EMT per NEC 358.10 (B). 4. Note 2 and annotation on Sheet E2 are N/A. 5. Put project address on all sheets. |