Permit Review Detail
Review Status: Completed
Review Details: ELECTRICAL
Permit Number - T04EL01620
Review Name: ELECTRICAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/06/2004 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T04EL01620 DENIED 8/4/04 1. Provide a disconnect at the parking garage per NEC 225.31 and 225.32. 2. Provide lighting fixture schedule and cut sheets. 3. Specify conductor size and type. 4. Specify conduit size and type. 5. The conductor powering Panel A is Service Entrance Conductor, not a feeder. Please correct on panel schedule. 6. The #4 between the meter and the service panel consists of a redundant path to ground. Please remove. 7. Provide TEP documentation of available fault current. 8. Provide for Equipment Grounding Conductor per NEC 250 Part VI. 9. Address Grounding Electrode requirements per NEC 250.32 for Two or More Buildings or Structures Supplied from a Common Service. |