Permit Number: T04EL01620
Parcel: 12209001C

Review Status: Completed

Review Details: ELECTRICAL

Permit Number - T04EL01620
Review Name: ELECTRICAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/06/2004 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T04EL01620 DENIED 8/4/04
1. Provide a disconnect at the parking garage per NEC 225.31 and 225.32.
2. Provide lighting fixture schedule and cut sheets.
3. Specify conductor size and type.
4. Specify conduit size and type.
5. The conductor powering Panel A is Service Entrance Conductor, not a feeder. Please correct on panel schedule.
6. The #4 between the meter and the service panel consists of a redundant path to ground. Please remove.
7. Provide TEP documentation of available fault current.
8. Provide for Equipment Grounding Conductor per NEC 250 Part VI.
9. Address Grounding Electrode requirements per NEC 250.32 for Two or More Buildings or Structures Supplied from a Common Service.