Permit Number: T04EL01600
Parcel: 117143570

Address:
510 W 18TH ST

Review Status: Completed

Review Details: ELECTRICAL

Permit Number - T04EL01600
Review Name: ELECTRICAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/02/2004 Linda Buczynski ELECTRICAL-COMMERCIAL REVIEW Denied TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL.

PLEASE CALL AT 791-5550 X1106 OR EMAIL AT Linda.Buczynski@tucsonaz.gov
IF YOU CARE TO DISCUSS.

1. Please provide fault calculations at any and all pertinent parts of the system.
2. It appears that the total for Service 2 Phase A is 108.3 A, not 15.3 A.

Final Status

Task End Date Reviewer's Name Type of Review Description
09/03/2004 DELMA ROBEY OUT TO CUSTOMER Completed