Permit Review Detail
Review Status: Completed
Review Details: ELECTRICAL
Permit Number - T04EL01528
Review Name: ELECTRICAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/13/2004 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T04EL01528 DENIED 8/13/04 1. Delete "Service" from "Service Panel A". 2. Provide overcurrent protection for Panel A feeder. 3. Delete "Ckts 2,4" from the 1 1/2" PVC. 4. Add Equipment Grounding conductor to the 1 1/2" PVC. 5. Determine whether this is to be a 60A SVC or a 200A SVC. Depict consistently on plans. 6. Modify "#A" to read "#4". |