Permit Number: T04EL01528
Parcel: 10607007B

Review Status: Completed

Review Details: ELECTRICAL

Permit Number - T04EL01528
Review Name: ELECTRICAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/13/2004 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T04EL01528 DENIED 8/13/04
1. Delete "Service" from "Service Panel A".
2. Provide overcurrent protection for Panel A feeder.
3. Delete "Ckts 2,4" from the 1 1/2" PVC.
4. Add Equipment Grounding conductor to the 1 1/2" PVC.
5. Determine whether this is to be a 60A SVC or a 200A SVC. Depict consistently on plans.
6. Modify "#A" to read "#4".