Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: ELECTRICAL
Permit Number - T04EL01504
Review Name: ELECTRICAL
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
07/22/2004 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T04EL01504 DENIED 7/22/04 1. Provide drawing with location of trailer panel and service disconnect. 2. Provide TEP available fault current. 3. Provide fault current rating of all equipment. 4. Indicate voltage, current, and phase. 5. Diagram grounding electrode system, with proper sizing of all components. |