Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T04EL01504
Parcel: 124041020

Review Status: Completed

Review Details: ELECTRICAL

Permit Number - T04EL01504
Review Name: ELECTRICAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/22/2004 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T04EL01504 DENIED 7/22/04
1. Provide drawing with location of trailer panel and service disconnect.
2. Provide TEP available fault current.
3. Provide fault current rating of all equipment.
4. Indicate voltage, current, and phase.
5. Diagram grounding electrode system, with proper sizing of all components.