Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T04EL01418
Parcel: Unknown

Review Status: Stopped

Review Details: ELECTRICAL

Permit Number - T04EL01418
Review Name: ELECTRICAL
Review Status: Stopped
Review Date Reviewer's Name Type of Review Description Status Comments
07/08/2004 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T04EL01418 DENIED 7/8/04

1. Indicate overcurrent protective devices for all branch circuits.
2. Provide overload protection for gate motors per NEC 430 Part III, or justify otherwise.
3. Provide Ground Fault and Short Circuit protection for motors per NEC 430 Part V.
4. Line Diagram configuration for motors does not correspond to panel schedule. Please clarify.
5. Provide for grounding electrode system per NEC 250.
6. Provide for lighting controls per IECC 805.2.2.
7. Exterior lighting shall have a source efficiency of at least 45 lumens per watt, per IECC 805.5. Incandescent is not acceptable.
8. Provide lighting fixture cut sheets to enable Plans Examiner to evaluate compliance with Lighting Ordinance.
9. There are several annotations referring to 40W and 70W lighting on the plan view, but line diagram and load calculations only consider 60W fixtures. Please clarify.
10. Indicate conduit runs on drawing, and depth of conduit fill.
07/08/2004 PETER MCLAUGHLIN ZONING REVIEW Approved
07/13/2005 DSTARK1 FIRE REVIEW Stop