07/08/2004 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved T04EL01399 DENIED 7/6/04

1. Since there is mechanical work, there shall be a permit for mechanical as well. Coordinate with Mechanical.
2. Project address shall go on plans.
3. Panel AC schedule indicates that it is MLO. Please indicate the 100A CB on panel schedule.
4. AC units on Ckts AC-7,9,11 and AC-2,4,6 have different current ratings on the plan and panel schedule. Please clarify, and double check fuse sizing for overload protection, typical.