Permit Number: T04EL01273
Parcel: 12108001B

Review Status: Completed

Review Details: ELECTRICAL

Permit Number - T04EL01273
Review Name: ELECTRICAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/16/2004 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T04EL01273 DENIED 6/16/04
1. Minimum font size shall be 10 point, which is slightly over 1/8".
2. Provide panel and circuit number for all new electrical loads.
3. Provide panel schedule and load calculations.
4. Provide conduit and conductor specifications.
5. Plans shall be prepared by a Registrant in the State of Arizona.