Permit Review Detail
Review Status: Completed
Review Details: ELECTRICAL
Permit Number - T04EL01273
Review Name: ELECTRICAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 06/16/2004 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T04EL01273 DENIED 6/16/04 1. Minimum font size shall be 10 point, which is slightly over 1/8". 2. Provide panel and circuit number for all new electrical loads. 3. Provide panel schedule and load calculations. 4. Provide conduit and conductor specifications. 5. Plans shall be prepared by a Registrant in the State of Arizona. |