Permit Number: T04EL01058
Parcel: 118121000

Review Status: Completed

Review Details: ELECTRICAL

Permit Number - T04EL01058
Review Name: ELECTRICAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/25/2004 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved T04EL01058 DENIED 5/19/04
1. Please provide panel schedule for new Panel A.
2. Indicate whether Panel A has a Main or is MLO.
3. Panel A is listed as 120/240V served by 120/208V 3-phase. Please clarify.
4. The GND in Feeder 3 provides a redundant path to ground and should be removed. The grounded conductor will be bonded to the service disconnecting means per NEC 250-22 (b).
5. The 3/0 in Feeder #2 also appears to be a redundant path to ground.