Permit Review Detail
Review Status: Completed
Review Details: ELECTRICAL
Permit Number - T04EL01058
Review Name: ELECTRICAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/25/2004 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Approved | T04EL01058 DENIED 5/19/04 1. Please provide panel schedule for new Panel A. 2. Indicate whether Panel A has a Main or is MLO. 3. Panel A is listed as 120/240V served by 120/208V 3-phase. Please clarify. 4. The GND in Feeder 3 provides a redundant path to ground and should be removed. The grounded conductor will be bonded to the service disconnecting means per NEC 250-22 (b). 5. The 3/0 in Feeder #2 also appears to be a redundant path to ground. |