Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T04EL00925
Parcel: 11615087J

Review Status: Completed

Review Details: ELECTRICAL

Permit Number - T04EL00925
Review Name: ELECTRICAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/20/2004 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved T04EL00925 DENIED 5/18/04
1. GND in feeders shall be sized according to the 400A fuse, and per Table 250-122 shall be no smaller than #3. Please evaluate conduit size to accommodate this change.
2. It appears that the generator should not be grounded as shown. With a 3-pole transfer switch, the neutral would not be switched, and therefore the generator does not consist of a derived system. Willing to discuss.