Review Details: ELECTRICAL
Permit Number - T04EL00925
Review Name: ELECTRICAL
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
05/20/2004 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Approved | T04EL00925 DENIED 5/18/04 1. GND in feeders shall be sized according to the 400A fuse, and per Table 250-122 shall be no smaller than #3. Please evaluate conduit size to accommodate this change. 2. It appears that the generator should not be grounded as shown. With a 3-pole transfer switch, the neutral would not be switched, and therefore the generator does not consist of a derived system. Willing to discuss. |