Permit Review Detail
Review Status: Completed
Review Details: ELECTRICAL
Permit Number - T04EL00380
Review Name: ELECTRICAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 02/26/2004 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Approved | T04ELDENIED 2/25/04 1. There are 3 receptacles on Ckt 29. Per NEC 220-3 (b) (9), they shall be counted as no less than 180 VA per receptacle. 2. There are 4 receptacles on Ckt 27. Per NEC 220-3 (b) (9), they shall be counted as no less than 180 VA per receptacle. 3. There are 2 receptacles on Ckt 21. Per NEC 220-3 (b) (9), they shall be counted as no less than 180 VA per receptacle. 4. There are 3 receptacles on Ckt 25. Per NEC 220-3 (b) (9), they shall be counted as no less than 180 VA per receptacle. 5. There are 3 receptacles on Ckt 23. Per NEC 220-3 (b) (9), they shall be counted as no less than 180 VA per receptacle. 6. There are 2 receptacles on Ckt 31. Per NEC 220-3 (b) (9), they shall be counted as no less than 180 VA per receptacle. 7. There are 8 receptacles with no panel or circuit designation. Provide such designation, or justify otherwise. |