Permit Review Detail
Review Status: Completed
Review Details: ELECTRICAL
Permit Number - T04EL00051
Review Name: ELECTRICAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/19/2004 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T04EL00051 DENIED 4/19/04 1. Fault calculations appear to be correct. Now rate panels accordingly. Panel A, at which AFC is 10,828, shall not be rated at 10K. Panel B, at which AFC is 14,360, shall not be rated at 10K. Make the necessary changes on the panel schedules. 2. Please eliminate the #4 ground in the conduits between the new disconnects and the meter, per the previous comment. This comment was made on the previous review. 3. Please see the attached from the State Board of Technical Registration. Changes to sealed drawings shall be dated. Please call at 791.5550 x1106 if you have any questions. |