Permit Number: T04EL00051
Parcel: 10712226B

Address:
2821 N STONE AV

Review Status: Completed

Review Details: ELECTRICAL

Permit Number - T04EL00051
Review Name: ELECTRICAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/13/2004 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T04EL00051 DENIED 4/13/04
1. Bussman up/over/down method is not acceptable to apply to downstream panels. Rework fault calculations and rate panels accordingly.
2. Please eliminate the #4 ground in the conduits between the new disconnects and the meter, per the previous comment.