Permit Review Detail
Review Status: Completed
Review Details: ELECTRICAL
Permit Number - T04EL00051
Review Name: ELECTRICAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/08/2004 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T04EL00051 DENIED 4/8/04 1. Please eliminate the GND in the conduit between the meter and the disconnect as a parallel path to ground. See NEC 250-24 (b). 2. Grounding Electrode Conductor shall be sized per NEC Table 250-66. 600 kcmil requires 1/0, not #4. 3. Per Bussman SPD, "c" value for 600 kcmil (non-metallic) is 28033, not 22965. Please correct, or justify otherwise. 4. Panel feeders are 3/0 in plan view, but #3 on line diagram. Please clarify. 5. Feeder conductors, #3, are not properly protected by 200A fuses. 6 The AFC ratings of the panels, at 10 KAIC, are not sufficient. |