Permit Number: T04EL00051
Parcel: 10712226B

Address:
2821 N STONE AV

Review Status: Completed

Review Details: ELECTRICAL

Permit Number - T04EL00051
Review Name: ELECTRICAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/29/2004 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied DENIED 1/21/04 T04EL00051

1. Can not install overhead service unless the existing service is overhead. Plans do not clarify that. Please indicate such on plans.
2. Since AFC is 12,685A at the panel, the 10,000A rating is insufficient. Please correct.
3. Feeder to new panel does not have overcurrent protection. Please clarify whether this is to be a fuse or a breaker, and provide current and fault current rating.
4. Eliminate the 1/0 GND between the meter and the service disconnect, as it constitutes a parallel path to ground.
5. NEC 220-30 is applicable to dwelling units, not commercial. Please remove such reference from the Service Load Calculation. Otherwise, the calculation itself is acceptable.

Please call at 791-5550 x1106, or email at lbuczyn1@ci.tucson.az.us if you have any questions.