Review Details: ELECTRICAL
Permit Number - T04EL00015
Review Name: ELECTRICAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/26/2004 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL. PLEASE CALL AT 791-5550 X1106 OR EMAIL AT LBUCZYN1@CI.TUCSON.AZ.US IF YOU CARE TO DISCUSS. 1. Please provide more information on the heaters, to enable evaluation of a disconnect switch. Are they with/without motors, unit switches, and supplementary OC protection? 2. Provide laundry circuits per NEC 210-52 (f), and outdoor outlets per 210-52 (e), or justify otherwise. 3. Protect bedroom branch circuits with Arc-Fault Circuit Interrupters, per NEC 210-12. 4. Provide bedroom wall-switch controlled outlets per NEC 210-70. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 02/11/2004 | TAMI ACHONG | OUT TO CUSTOMER | Completed |
| 02/11/2004 | TAMI ACHONG | REJECT SHELF | Completed |