Permit Number: T04EL00015
Parcel: 119041400

Review Status: Completed

Review Details: ELECTRICAL

Permit Number - T04EL00015
Review Name: ELECTRICAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/26/2004 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL.

PLEASE CALL AT 791-5550 X1106 OR EMAIL AT LBUCZYN1@CI.TUCSON.AZ.US
IF YOU CARE TO DISCUSS.

1. Please provide more information on the heaters, to enable evaluation of a disconnect switch. Are they with/without motors, unit switches, and supplementary OC protection?
2. Provide laundry circuits per NEC 210-52 (f), and outdoor outlets per 210-52 (e), or justify otherwise.
3. Protect bedroom branch circuits with Arc-Fault Circuit Interrupters, per NEC 210-12.
4. Provide bedroom wall-switch controlled outlets per NEC 210-70.

Final Status

Task End Date Reviewer's Name Type of Review Description
02/11/2004 TAMI ACHONG OUT TO CUSTOMER Completed
02/11/2004 TAMI ACHONG REJECT SHELF Completed