Permit Number: T04CM05627
Parcel: 14108521C

Review Status: Completed

Review Details: POST 3RD PARTY REVIEW

Permit Number - T04CM05627
Review Name: POST 3RD PARTY REVIEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
12/10/2007 MARTIN BROWN FIRE REVIEW Denied Design criteria on cover sheet is not valid. NFPA 231 and 231C no longer exist. Please include all relevant design information, including but not limited to, commodity classification(s), height of storage, height of building, aisle width between racks, design table and curve from NFPA 13, 2002 Edition, etc.

Final Status

Task End Date Reviewer's Name Type of Review Description
12/11/2007 VFLORES1 OUT TO CUSTOMER Completed
12/11/2007 VFLORES1 REJECT SHELF Completed