Permit Review Detail
Review Status: Completed
Review Details: POST 3RD PARTY REVIEW
Permit Number - T04CM05627
Review Name: POST 3RD PARTY REVIEW
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 12/10/2007 | MARTIN BROWN | FIRE | REVIEW | Denied | Design criteria on cover sheet is not valid. NFPA 231 and 231C no longer exist. Please include all relevant design information, including but not limited to, commodity classification(s), height of storage, height of building, aisle width between racks, design table and curve from NFPA 13, 2002 Edition, etc. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 12/11/2007 | VFLORES1 | OUT TO CUSTOMER | Completed |
| 12/11/2007 | VFLORES1 | REJECT SHELF | Completed |