Review Details: RESUBMITTAL
Permit Number - T04CM05625
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/09/2005 | NEAL SAUNDERS | BUILDING-RESIDENTIAL | REVIEW | Denied | 1. Provide rebar at top of stemwall on Cross-section on page 5. 3. Detail interior footing. Dimension width, depth and rebar reinforcement. 4. 4x4 beam and 4x6 beams are inadequate for spans and tributary widths. 4x6) 9' span, 6' trib - 4x4) 9' span, 7' trib. Consider a 3-1/8"x6 GLB in place of each beam. 5. Specify rafter to beam connection @ end of porch. 6. 1/4 - Clarify connection of ledger board to bent bolt. Consider bearing 2x6 porch rafter on top plate of CMU wall or just face mount rafters to 4x8 beam that is connected to CMU wall as shown on section on page 5. 7. Load calcs are not complete. There is no load shown for bath circuit, water heater or AC unit. provide per E3502.2 ANY QUESTIONS CONTACT NEIL SAUNDERS 791-5550 x 1113. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 08/12/2005 | GBONILL1 | OUT TO CUSTOMER | Completed |
| 08/12/2005 | SUE REEVES | REJECT SHELF | Completed |