Permit Review Detail
Review Status: Completed
Review Details: RESIDENTIAL BLDG/WWM
Permit Number - T04CM05625
Review Name: RESIDENTIAL BLDG/WWM
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 03/15/2005 | GERRY KOZIOL | WWM | REVIEW | Approved | |
| 03/24/2005 | NEAL SAUNDERS | BUILDING-RESIDENTIAL | REVIEW | Denied | Plan Check Comments - Project T04CM05625 Plan Review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, we request that you please provide revised plans and calculations, highlighting any changes, along with a written response to each of the noted items indicating action taken. General Requirements 1. All corrections and revisions shall be made on the original tracings and two new sets of prints or (1) sepia and (1) blue line shall be returned. 2. Pen or pencil corrections on final prints will not be acceptable. To avoid delays ensure that corrections have been made, are complete and have been coordinated on all-applicable details and notes. Foundation Plan 1. 1/3 - Provide #4 rebar at top of stemwall. Also, "Horizontal rief. 16" o/c full height 32" o/c"? Clarify. 2. 2/3 - Post footing minimum size is 12" square with 12" into undisturbed soil. 6" separation from finish grade to post. Provide these dimensions and specify post base (ABA 44?). Floor Plan 1. Specify operable portion of each window (XO). 2. Show that each water closet is located in a clear space not less than 30" wide and has a clear space in front not less than 21" per figure R307.2. 3. Identify ceiling heights in all areas on floor plan. If sloped ceiling, note average height. Structural Plan 1. Header schedule - How will (2) 2x headers fit into 2x2 furr out? Clarify. Steel lintels are all that is necessary at openings as the masonry wall is the bearing structure. 2. 4x8-ridge beam is inadequate for span and tributary width. Resize. Consider GluLam beam. 3. 2x8 rafters at 24" o/c with 20psf (live) and 15 psf (dead) loads are overspaned. Max distance is 13'-10". 4. Provide porch rafter to beam connection detail. 5. Specify top plate at non-bearing wall. 6. Note and specify a complete roofing system: Roofing type, grade of materials and method of installation per R905. Plumbing Plan 1. Specify clearance from foundation to two-way cleanout (2'). 2. Provide fixture count for existing house. Specify quantity of each fixture and total fixture units that are existing. 3. Note that bathtub and shower enclosures shall be finished per P2710 with ceramic tile, or a listed enclosure, to a height of 72" above the drain per R702.4 and R307.2. 4. Note on plan compliance with the water conservation requirements. Water closets, 1.6 gallons per flush, sinks and showerheads, 3 gallons per minute. 5. Note on plans that shower and tub / shower combinations that have individual control valves shall be of the pressure balance or thermostatic mixing valve type. Electrical Plan 1. Size feeder lines to sub-panel and appropriate breaker size in existing panel. 2. Is tankless water heater 110v? Typically these heaters require 220v thus occupying two panel spaces. Clarify. 3. Specify AC load and locate appropriate equipment circuits on plan and in panel schedule. 4. Specify total load on new subpanel in Amps. Include AC load. MODEL ENERGY CODE: 1. Provide energy calculations per the 1998 IECC and comply with IRC chapter 11 or percentage method (attached to plans) that support chosen values. 3. How will R-19 in walls be achieved with 2x2 furr out? 4. 3/4 - Insulation is called out as R-22, which is correct for 2x8 space however R-30 is called out on another sheet. Clarify. If you have any questions, please contact your assigned plans examiner Neil Saunders at 791-5550, extension 1113. NOTE: As of 09/06/04 the City of Tucson has adopted the 2003 IRC with the exception of the plumbing portion which has been replaced with the Arizona state plumbing code. All model plans shall reference these codes. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 03/29/2005 | BETH GRANT | OUT TO CUSTOMER | Completed |
| 03/29/2005 | SUE REEVES | REJECT SHELF | Completed |