Permit Number: T04CM05616
Parcel: Unknown

Review Status: Completed

Review Details: COMMERCIAL-BLDG/FIRE ONLY

Permit Number - T04CM05616
Review Name: COMMERCIAL-BLDG/FIRE ONLY
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/06/2005 CHRISTY FOREMAN BUILDING-COMMERCIAL REVIEW Passed STRUCTURAL NOT REQUIRED IN SCOPE OF WORK.
01/06/2005 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved T04CM05616 DENIED 12/30/04

1. Provide TEP available fault current, and fault current rating of equipment.
2. Provide size of grounding electrode conductor.
3. Provide overload protection for gates per NEC 430 Part III.
4. Provide ground fault and short circuit protection for gates per NEC Part IV.
5. Show source of TEP power on plans.
6. Put power requirements for gates on plans.
01/06/2005 JIM EGAN FIRE REVIEW Approved
12/30/2004 BLANCA ESPINO ENGINEERING REVIEW Approved
12/30/2004 PATRICIA GEHLEN ZONING REVIEW Approved