Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL-BLDG/FIRE ONLY
Permit Number - T04CM05616
Review Name: COMMERCIAL-BLDG/FIRE ONLY
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/06/2005 | CHRISTY FOREMAN | BUILDING-COMMERCIAL | REVIEW | Passed | STRUCTURAL NOT REQUIRED IN SCOPE OF WORK. |
| 01/06/2005 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Approved | T04CM05616 DENIED 12/30/04 1. Provide TEP available fault current, and fault current rating of equipment. 2. Provide size of grounding electrode conductor. 3. Provide overload protection for gates per NEC 430 Part III. 4. Provide ground fault and short circuit protection for gates per NEC Part IV. 5. Show source of TEP power on plans. 6. Put power requirements for gates on plans. |
| 01/06/2005 | JIM EGAN | FIRE | REVIEW | Approved | |
| 12/30/2004 | BLANCA ESPINO | ENGINEERING | REVIEW | Approved | |
| 12/30/2004 | PATRICIA GEHLEN | ZONING | REVIEW | Approved |