Permit Number: T04CM05559
Parcel: 12809005E

Address:
5353 E 22ND ST

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T04CM05559
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/04/2005 BOB SUBA ELECTRICAL-COMMERCIAL REVIEW Approved
04/05/2005 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied The provided calculations (Mechanical Note #4, Sheet 5) do not address this issue; see Chapter 8, IECC 2000. Provide calculations to show that the addition complies with Section 101.3, IECC 2000.
04/05/2005 ROBERT SHERRY WATER REVIEW Approved
04/05/2005 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
04/11/2005 PATRICIA GILBERT ENGINEERING REVIEW Approved
04/18/2005 CHRISTY FOREMAN BUILDING-COMMERCIAL REVIEW Approved CITY OF TUCSON DEVELOPMENT SERVICES
STRUCTURAL REVIEW COMMENTS

DATE: 4/20/05
ACTIVITY NUMBER: T04CM05330 & T04CM05559
PROJECT NAME: Exercise Room & Addition Business Office
PROJECT ADDRESS: 5353 E 22 ND St. #101
ARCHITECT / ENGINEER: Antonio Romano
PROJECT REVIEWER: Christy Foreman



TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL.

PLEASE CALL AT 791-5550 X1108 OR EMAIL AT CFOREMA1@CI.TUCSON.AZ.US IF YOU CARE TO DISCUSS.

1) Separated use 2 hour separation between B and R2 use. Please clarify / locate and provide wall section / ceiling section. Clarify how you are achieving 2 hr. Justify per UL (underwriting laboratories) listing.
2) Detail connection of beam 5 1/8" x 12" GLM beam at existing wall. Clarify bearing of Glulam beam to carry load to footing. Column?
04/29/2005 PETER MCLAUGHLIN ZONING REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
05/05/2005 KMEDINA1 OUT TO CUSTOMER Completed