Permit Number: T04CM05559
Parcel: 12809005E

Address:
5353 E 22ND ST

Review Status: Completed

Review Details: COMMERCIAL NEW

Permit Number - T04CM05559
Review Name: COMMERCIAL NEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/04/2005 JIM EGAN FIRE REVIEW Approved
02/07/2005 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed
02/07/2005 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Provide calculations to show that the addition complies with Section 101.3, IECC 2000.
2. Show all modifications to the mechanical systems and show the new air conditioner.
3. Provide calculations to show that the ventilation for the space conforms to Section 401, IMC 2000.
02/07/2005 ROBERT SHERRY WATER REVIEW Approved
02/14/2005 BOB SUBA ELECTRICAL-COMMERCIAL REVIEW Approved
02/23/2005 GERRY KOZIOL WWM REVIEW Passed
03/07/2005 CHRISTY FOREMAN BUILDING-COMMERCIAL REVIEW Denied CITY OF TUCSON DEVELOPMENT SERVICES
STRUCTURAL REVIEW COMMENTS

DATE: 3/1/05
ACTIVITY NUMBER: T04CM05330 & T04CM05559
PROJECT NAME: Exercise Room & Addition Business Office
PROJECT ADDRESS: 5353 E 22 ND St. #101
ARCHITECT / ENGINEER: Antonio Romano
PROJECT REVIEWER: Christy Foreman



TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL.

PLEASE CALL AT 791-5550 X1108 OR EMAIL AT CFOREMA1@CI.TUCSON.AZ.US IF YOU CARE TO DISCUSS.

1) Need to have a complete site plan showing all buildings. Locate on site the building that is being remodeled. Dimensions from other buildings. Justify per code section 302.3.2.
2) Separated use 2 hour separation between B and R2 use. Please clarify / locate and provide wall section.
3) Exercise room A-3 use? See section 302.2.1. Please clarify / justify.
4) Separated use see table 302.3.2, 2 hr. fire separation required between a B use and R2/A3. Please clarify / justify.
5) Detail connection of beam 5 1/8" x 12" GLM beam at existing wall.
6) Clarify exercise room 1 story or 2 story structure. Provide calculations accordingly. Beams carrying roof and flooring load?
7) Clarify existing roof framing direction of spans by rafters / floor joists. Existing office and exercise room.
8) Clarify location of shear walls and detail on drawings..
9) Clarify accessibility Chapter 11 accessible route section 1104.
10) Justify / clarify per section 903.2.7 & 907.2.10.1.2.
11) Structural Engineer need to review and stamp sht. 4/4.
03/10/2005 PETER MCLAUGHLIN ZONING REVIEW Denied The approved site plan shows a pedestrian sidewalk connecting to the sidewalk located within the existing right-of-way along 22nd Street. This ped. connection is required and the 5-foot pedestrian refuge shown on the partial site plan must also include a 4-foot sidewalk. Revise plan to show accessible pedestrian route between the new addition and the PAAL. Also, for reference, show the parking spaces as they exist within the vehicle use area shown on the partial site plan.

Final Status

Task End Date Reviewer's Name Type of Review Description
03/28/2005 TAMI ACHONG OUT TO CUSTOMER Completed
03/28/2005 ANGIE SHOFFSTALL REJECT SHELF Completed