01/27/2005 Terry Stevens BUILDING-RESIDENTIAL REVIEW Denied PLAN REVIEW COMMENTS PROJECT #T04CM05558
01/27/05

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, we request that you please provide revised plans and calculations, highlighting any changes, along with a written response to each of the noted items indicating action taken.
SCOPE OF REVIEW:
The scope of this plan review covers architectural, plumbing, mechanical, model energy and electrical. All code references are to the 2003 International Residential Code, 2000 International Energy Conservation Code, and Arizona State Plumbing Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval.
GENERAL REQUIREMENTS:
1. All corrections and revisions shall be made on the original tracings and two new sets of prints or (1) sepia & (1) blue line shall be returned along with all redline prints. Pen or pencil corrections on final prints will not be acceptable. To avoid delays, ensure that all corrections have been made, are complete, and have been coordinated on all applicable detail and note sheets.
FOUNDATION PLANS:
1. Provide foundation plan for ramada.
2. Dimension the wall thickness, footing width thickness and depth into undisturbed soil for each footing type and condition per IRC table R403.1.-------for ramada
3. Locate and detail all footings for the following:
- posts
4. Locate and specify all post anchors on the foundation plan.
5. All foundation hold-downs and anchor-bolt spacing for brace walls shall be specified and located.---------PAHD42 hold down when used with in 8" of a corner does not have the required uplift value of 1800#-------a HPAHD22 meets this requirement
STRUCTURAL PLANS:
1. The 2-2x10 header over "manual door" appears to be inadequate for loads imposed. Change or submit calcs.
2. The insulation indicated on section A-A cannot be up against the bottom of roof sheathing when asphalt shingles are used. A min. 11/2" vent space is required.
3. Completely detail all connections and cross-reverence to the foundation and framing plans:
- Post to slab----indicate post base type
PLUMBING PLANS:
1. Note and specify all piping materials.
2. Note that bathtub and shower enclosures shall be finished per P2710 with ceramic tile, or a listed enclosure, to a height of 72" above the drain per R702.4 and R307.2.
ELECTRICAL PLANS:
1. Feeders to subpanel indicate 2-#4 cu, 3-#4cu are required to provide 220v inidcated.
If you have any questions, please contact your assigned plans examiner Terry Stevens at 791-5550, extension 1112.