Permit Number: T04CM05544
Parcel: 13414011A

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T04CM05544
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/03/2005 Robert Sherry PLUMBING-COMMERCIAL REVIEW Denied 1. Revise the waste and vent piping shown in riser detail 2/P1 to comply with Section 908.1.
2. Show how the water piping was sized.
01/03/2005 ROBERT SHERRY WATER REVIEW Approved
01/03/2005 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Show the source of make up water for the cooling tower and its backflow protection.
2. Provide protection from the sun for the PVC (piping on the cooling tower) exposed to the sun.
3. Provide information from the dryer manufacturer that the 3-1/2"x 6" duct is suitable.
4. Show the amount of outside air to be used for the new fitness room conforms to the requirements of Section403.3, IMC 2000.
01/19/2005 Linda Buczynski ELECTRICAL-COMMERCIAL REVIEW Denied TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL.

PLEASE CALL AT 791-5550 X1106 OR EMAIL AT Linda.Buczynski@tucsonaz.gov
IF YOU CARE TO DISCUSS.

1. Please clarify Input VA for lighting fixtures, esp. Fixture A. It does not appear that continuous load has been accounted for in Ckts A-2, A-4, A-6, A-8, A-10, A-13.
2. Line diagram shows 1/0 (ampacity 150) protected by 200 Afs in (4) places. A 400 AF protects #6, and 250 MCM is protected by a 60 AF. Please clarify.
3. Ckt K-9, new power pole. No load on panel schedule.
01/28/2005 Raul Palma BUILDING-COMMERCIAL REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
02/03/2005 DELMA ROBEY OUT TO CUSTOMER Completed