Review Details: COMMERCIAL TI
Permit Number - T04CM05544
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/03/2005 | Robert Sherry | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Revise the waste and vent piping shown in riser detail 2/P1 to comply with Section 908.1. 2. Show how the water piping was sized. |
| 01/03/2005 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 01/03/2005 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Show the source of make up water for the cooling tower and its backflow protection. 2. Provide protection from the sun for the PVC (piping on the cooling tower) exposed to the sun. 3. Provide information from the dryer manufacturer that the 3-1/2"x 6" duct is suitable. 4. Show the amount of outside air to be used for the new fitness room conforms to the requirements of Section403.3, IMC 2000. |
| 01/19/2005 | Linda Buczynski | ELECTRICAL-COMMERCIAL | REVIEW | Denied | TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL. PLEASE CALL AT 791-5550 X1106 OR EMAIL AT Linda.Buczynski@tucsonaz.gov IF YOU CARE TO DISCUSS. 1. Please clarify Input VA for lighting fixtures, esp. Fixture A. It does not appear that continuous load has been accounted for in Ckts A-2, A-4, A-6, A-8, A-10, A-13. 2. Line diagram shows 1/0 (ampacity 150) protected by 200 Afs in (4) places. A 400 AF protects #6, and 250 MCM is protected by a 60 AF. Please clarify. 3. Ckt K-9, new power pole. No load on panel schedule. |
| 01/28/2005 | Raul Palma | BUILDING-COMMERCIAL | REVIEW | Approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 02/03/2005 | DELMA ROBEY | OUT TO CUSTOMER | Completed |