Permit Number: T04CM05544
Parcel: 13414011A

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T04CM05544
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
12/22/2004 JIM EGAN FIRE REVIEW Approved
12/22/2004 MICHAEL ST. PAUL ZONING REVIEW Approved
12/22/2004 PATRICIA GILBERT ENGINEERING REVIEW Approved
12/23/2004 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Revise the waste and vent piping shown in riser detail 2/P1 to comply with Section 908.1.
2. Show how the water piping was sized.
12/23/2004 CHRISTY FOREMAN BUILDING-COMMERCIAL REVIEW Needs Review
12/23/2004 GERRY KOZIOL WWM REVIEW Approved
12/23/2004 DROBEY1 ELECTRICAL-COMMERCIAL REVIEW Needs Review
12/23/2004 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Show the source of make up water for the cooling tower and its backflow protection.
2. Provide protection from the sun for the PVC (piping on the cooling tower) exposed to the sun.
3. Provide information from the dryer manufacturer that the 3-1/2"x 6" duct is suitable.
4. Show the amount of outside air to be used for the new fitness room conforms to the requirements of Section403.3, IMC 2000.
12/23/2004 ROBERT SHERRY WATER REVIEW Approved