Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T04CM05544
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 12/22/2004 | JIM EGAN | FIRE | REVIEW | Approved | |
| 12/22/2004 | MICHAEL ST. PAUL | ZONING | REVIEW | Approved | |
| 12/22/2004 | PATRICIA GILBERT | ENGINEERING | REVIEW | Approved | |
| 12/23/2004 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Revise the waste and vent piping shown in riser detail 2/P1 to comply with Section 908.1. 2. Show how the water piping was sized. |
| 12/23/2004 | CHRISTY FOREMAN | BUILDING-COMMERCIAL | REVIEW | Needs Review | |
| 12/23/2004 | GERRY KOZIOL | WWM | REVIEW | Approved | |
| 12/23/2004 | DROBEY1 | ELECTRICAL-COMMERCIAL | REVIEW | Needs Review | |
| 12/23/2004 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Show the source of make up water for the cooling tower and its backflow protection. 2. Provide protection from the sun for the PVC (piping on the cooling tower) exposed to the sun. 3. Provide information from the dryer manufacturer that the 3-1/2"x 6" duct is suitable. 4. Show the amount of outside air to be used for the new fitness room conforms to the requirements of Section403.3, IMC 2000. |
| 12/23/2004 | ROBERT SHERRY | WATER | REVIEW | Approved |