Permit Number: T04CM05542
Parcel: 121110490

Review Status: Completed

Review Details: REVISION

Permit Number - T04CM05542
Review Name: REVISION
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/03/2005 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved T04CM05542 DENIED 2/3/05
1. Modify drawings to indicate new lighting fixture schedule.
2. Information On Electric Symbol/Lighting Legend does not correspond to new fixture schedule.
3. Ckt 1, with (12) (50) W lights, should have (600) (1.25) = 750VA, not 360.
4. Wireway A and B appear to be mixed up on the Load Summary.