Permit Number: T04CM05536
Parcel: 119280950

Address:
2601 W ARTHUR PL

Review Status: Completed

Review Details: SITE

Permit Number - T04CM05536
Review Name: SITE
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/16/2005 JIM EGAN FIRE REVIEW Approved
08/18/2005 LOREN MAKUS ENGINEERING REVIEW Denied T04CM05536
1. A Grading plan and permit are required. This project does not meet the exemption criteria of Development Standard 11-01.2.3. The drainage report exhibits indicate that fill will be placed in areas with slopes that exceed 20 per cent. Provide a complete grading permit submittal with a grading plan showing the extent of work and details describing the toe down and tie in for the bank protection. The plan must be drawn to scale and the specifications for the bank protection must be included in the drainage report or in a separate report provided by a registered professional engineer. The plan must also show the extent of the floodplain.
2. The drainage report indicates that the bank will be protected with gunnited rock riprap. Revise the drainage report to provide sizing and embedding details and design criteria for the bank protection. The design must be consistent with the flow velocities indicated in the drainage report.

If you have any questions contact me at loren.makus@tucsonaz.gov or at 791-5550 ext 1161.

Loren Makus, E.I.T.
Senior Engineering Associate
08/25/2005 PETER MCLAUGHLIN NPPO REVIEW Approved
08/25/2005 JOE LINVILLE LANDSCAPE REVIEW Passed Landscaping will approve plan when the engineering division has completed its review.
08/25/2005 JOE LINVILLE LANDSCAPE REVIEW Passed Landscaping defers to engineering and zoning for SFR.
09/17/2005 TERRY STEVENS ZONING HC SITE REVIEW Passed see zoning comments
09/17/2005 TERRY STEVENS ZONING REVIEW Denied DSD TRANSMITTAL

FROM: Terry Stevens FOR: David Rivera
Senior Planner Principal Planner

PROJECT:T04CM05536
2601 W. Arthur Pl.
New SFR
Site Plan

Transmittal date: 3rd Review 9-17-05

COMMENTS: Please resubmit revised drawings along with redlines and a response letter, which states how all Zoning Review Section comments regarding the Land Use Code and Development Standards were addressed.

1. The plans submitted do not meet the criteria required for a site plan. See attached site plan example and criteria required. Submitted plans must be legible


If you have any questions about this transmittal, please call Terry Stevens, (520) 791-5550 ext. 2000.

Final Status

Task End Date Reviewer's Name Type of Review Description
10/31/2005 SUE REEVES REJECT SHELF Completed
09/27/2005 JMORALE1 OUT TO CUSTOMER Completed