Permit Number: T04CM05536
Parcel: 119280950

Address:
2601 W ARTHUR PL

Review Status: Completed

Review Details: SITE

Permit Number - T04CM05536
Review Name: SITE
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/06/2005 Andrew Connor LANDSCAPE REVIEW Denied Development shall not unnecessarily alter riparian habitats of watercourses and adjacent bank areas per TCC Sec. 26-5.1.Submit any requested documentation by the engineering division to continue landscape review.
01/06/2005 ANDREW CONNOR NPPO REVIEW Passed
01/24/2005 David Rivera ZONING REVIEW Denied 01/24/05

Development Services Department
Zoning Review Section

David Rivera
Senior Planner

Comments

1. The residential site/building plans have been reviewed but cannot be approved at this time. The following criteria must be addressed.

a. G. For any new single family dwelling in the R-1 zone with five (5) bedrooms, three (3) parking spaces are required. For every bedroom over five (5), one additional space is required for each bedroom.
H. For all single family dwellings in the R-1 zone with five (5) or more bedrooms, and for all lots containing two (2) or more single family dwellings, with the second dwelling having more than one bedroom, all parking and maneuvering must be located on-site, either in a side or rear perimeter yard. The vehicular use area must be improved, which includes surfacing, striping, and provision of barriers, in conformance with Development Standard 3-05.0. Parking spaces may not be located in a vehicular use area in any front
street perimeter yard.

This site must be developed to comply with the criteria as specified.

2. Submit a copy of the building plans which include a floorplan and building elevations.
01/24/2005 DAVID RIVERA ZONING HC SITE REVIEW Passed
01/28/2005 Doug Williams ENGINEERING REVIEW Denied SUBJECT: Hydrology data and Floodplain permit review comments - 2601 W. Arthur Pl.
REVIEWER: Doug Williams
DATE: 28 January 2005
ACTIVITY NUMBERS: T04CM05536/T04OT02495
T14S, R13E, Section 28

Resubmittal Required: Revised Site Plan and Hydrology report.

SUMMARY: Engineering Division has reviewed the subject plans and drainage submittal. Approvals are not recommended at this time. Proposed development in the regulatory floodplain must conform to Chapter 26, Tucson Code. Particular attention should be given to Sections 26-5.2, 26-7 and 26-11. The drainage submittal must conform to Hydrology Report format and content requirements outlined in Section 2.3.1 of the City of Tucson's Standards Manual for Drainage Design and Floodplain Management (Development Standard 10-02.0). Additional information may be necessary prior to approvals, depending on the nature and extent of subsequent plan revisions. Please address the following comments at a minimum, prior to resubmittal:

1. Depict the existing and developed conditions 100-year (regulatory) floodplain limits, with water surface elevations provided at the upstream-most portion of the proposed structure.
2. Provide all supporting data for Manning's cross-sections and floodplain delineations for existing and developed conditions (see summary above relating to hydrology report content requirements)
3. Provide an encroachment analysis demonstrating no adverse impact will occur to adjacent properties - upstream or downstream or in the public right of way.
4. Provide a cross-section at the property line/driveway entrance with depth of flow indicated, demonstrating all weather access will be provided on this lot.
5. Provide dimensioning for the proposed overhang's footing dimensions and depths, and revise the bank protection detail (A) to match detail (B).
6. Provide estimated cut and fill quantities.
7. Provide a soils and geotechnical engineering evaluation/report.

A grading permit will be required for this proposed development. Submit two (2) sets of grading plans with a grading permit application. No clearing, grubbing or other earthwork is permitted on this site prior to grading permit issuance. Site grading shall be in conformance with the Development Standard 11-01.0 (Excavation and Grading). For further information, visit http://www.ci.tucson.az.us/dsd/DevStd1101.pdf

If you have any questions, I can be reached at 791-5550, extension 1189 or via email at Doug.williams@tucsonaz.gov

Douglas Williams
Sr. Engineering Associate
Engineering Division
Development Services Department
12/27/2004 JIM EGAN FIRE REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
01/31/2005 TAMI ACHONG OUT TO CUSTOMER Completed
01/31/2005 ANGIE SHOFFSTALL REJECT SHELF Completed