Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL NEW
Permit Number - T04CM05518
Review Name: COMMERCIAL NEW
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/03/2005 | Gerry Koziol | WWM | REVIEW | Approved | |
| 01/04/2005 | BOB SUBA | ELECTRICAL-COMMERCIAL | REVIEW | Approved | See comments on White Card. Pages missing. Electrical missing. According to Electrical Reviewer, Bob Suba, all he saw were the specifications. |
| 01/26/2005 | Raul Palma | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 12/23/2004 | Jim Egan | FIRE | REVIEW | Approved | |
| 12/29/2004 | Robert Sherry | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. This review is limited to the area of the new addition to the building. 2. Provide cleanouts in the modified building sewer at intervals not exceeding 100 feet and for aggregate horizontal change in direction exceeding 135 degrees. Reference Section 719.1, UPC 1994. 3. Clarify the meaning of the second Keynote 11 (pointing to the outlet of the grease trap). 4. Show the size and route for the vent for the grease trap. Reference Section 1001.1, UPC 1994. |
| 12/29/2004 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. This review is limited to the area of the new addition to the building. 2. Sign and seal the Compliance Statement for the energy conservation code calculations. 3. If the roof pitch is 3:12 or greater, provide a level platform for maintenance access to the evaporative cooler on the addition. Reference Section 306.6, IMC 2000. 4. Coordinate the rooftop equipment shown on drawings A1.4 and M1.0 (Relief hood or exhaust fan?). 5. Indicate the size for the new connector for the relocated water heater. Indicate the type of termination and the minimum termination height of the common flue. Reference Section 517.3, UPC 1994. |
| 12/29/2004 | ROBERT SHERRY | WATER | REVIEW | Approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 02/16/2005 | TAMI ACHONG | OUT TO CUSTOMER | Completed |
| 02/16/2005 | ANGIE SHOFFSTALL | REJECT SHELF | Completed |