Permit Number: T04CM05497
Parcel: Unknown

Address:
3737 E FLOWER ST

Review Status: Completed

Review Details: REVISION

Permit Number - T04CM05497
Review Name: REVISION
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/05/2005 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. The minimum slope for a 4" building sewer is 1/8" per foot. Reference Section 718.1, UPC 1994.
2. Show how the water piping was sized. Reference Section610.1, UPC 1994.
3. Provide reduced pressure backflow preventers after the water meters.
4. Show the materials of construction for the water and sewer piping.
05/11/2005 CAGUILA1 WWM REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
05/11/2005 CINDY AGUILAR APPROVAL SHELF Completed
05/11/2005 CINDY AGUILAR OUT TO CUSTOMER Completed