Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: OTHER
Permit Number - T04CM05483
Review Name: OTHER
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
12/28/2004 | PATRICIA GILBERT | ENGINEERING | REVIEW | Denied | DATE: December 28, 2004 ACTIVITY NUMBER: T04OT02482/T04CM05483/T04CM05484 PROJECT NAME: Elzey Residence PROJECT ADDRESS: 1009 & 1013 East Halcyon PROJECT REVIEWER: Patricia Gilbert FLOODPLAIN USE PERMIT IS DENIED RESUBMITTAL REQUIRED: SITE PLAN, DRAINAGE REPORT, FLOODPLAIN USE PERMIT APPLICATION 1. Specify on the site/plot plan the datum and the water surface elevation (WSE) in the hydrology report. Please note the datum used for the WSE and the Finish Floor Elevation (FFE) must match or a conversion needs to take place. 2. Label the FFE on the site plan that is given in the hydrology report. 3. Change each plan to reflect the correct address. 4. Include a note on the site plan that the site is in a FEMA Special Flood Hazard Zone AE. DS 2-02.2.1.A.15. 5. Please note a condition of this permit contains a requirement that the applicant, or the applicant's authorized representative, complete a FEMA Elevation Certificate and is returned to DSD Engineering prior to approval of special inspection. |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
12/28/2004 | SUE REEVES | OUT TO CUSTOMER | Completed |
12/28/2004 | SUE REEVES | REJECT SHELF | Completed |