Review Date Reviewer's Name Type of Review Description Status Comments
12/17/2004 PATRICIA GILBERT ENGINEERING REVIEW Approved
12/17/2004 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed
12/17/2004 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
12/17/2004 RAUL PALMA BUILDING-COMMERCIAL REVIEW Approved
12/17/2004 ROBERT SHERRY WATER REVIEW Approved
12/17/2004 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T04CM05458 DENIED 12/17/04
1. Service total is listed as 38,600 VA. This would be only 107.2 A at 208 V, which is smaller than Panel A. Please clarify.
2. Ckt A-38,40,42 reads "Panel A2". Should read "Panel A1."
3. It appears that the intent is to series rate the new CB at Panel A with the CBs at Panel A1. If so, make that explicit. Also: I would question the 10K rating of Panel A itself, being so close to the termination can (20.1 KA AFC).
4. Line diagram lists new CB at 60A. It is 50 A on Panel A. 50 A is correct because the ampacity of #8 is only 50.