Permit Number: T04CM05456
Parcel: 12105013B

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T04CM05456
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
12/17/2004 JIM EGAN FIRE REVIEW Approved
12/17/2004 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
12/17/2004 RAUL PALMA BUILDING-COMMERCIAL REVIEW Approved
12/17/2004 ROBERT SHERRY WATER REVIEW Approved
12/17/2004 PETER MCLAUGHLIN ZONING REVIEW Approved
12/17/2004 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Revise ventilation for AC-3 using Section 403.3.2, IMC 2000.
12/20/2004 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T04CM05456 DENIED 12/20/04

1. Circuit B-25 appears undercounted on panel schedule at 350 VA. I get 600 VA before adding Fixture C. Define VA requirements for Fixture C on Lighting Schedule and recalculate this branch circuit.
2. Please show Panel B location on plans.
3. The 100 A circuit powering Panel B is inadequate for the 127A load.
4. Provide load calculations for service entrance conductors.
5. Gutters and terminating cabinet at service entrance are to provided per the Line Diagram. It is unclear why this is so, considering the load side distribution equipment is existing.
12/21/2004 LLESNY1 WWM REVIEW Needs Review
12/21/2004 LLESNY1 ENGINEERING REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
12/21/2004 LISA LESNY OUT TO CUSTOMER Completed