Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T04CM05456
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 12/17/2004 | JIM EGAN | FIRE | REVIEW | Approved | |
| 12/17/2004 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Approved | |
| 12/17/2004 | RAUL PALMA | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 12/17/2004 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 12/17/2004 | PETER MCLAUGHLIN | ZONING | REVIEW | Approved | |
| 12/17/2004 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Revise ventilation for AC-3 using Section 403.3.2, IMC 2000. |
| 12/20/2004 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T04CM05456 DENIED 12/20/04 1. Circuit B-25 appears undercounted on panel schedule at 350 VA. I get 600 VA before adding Fixture C. Define VA requirements for Fixture C on Lighting Schedule and recalculate this branch circuit. 2. Please show Panel B location on plans. 3. The 100 A circuit powering Panel B is inadequate for the 127A load. 4. Provide load calculations for service entrance conductors. 5. Gutters and terminating cabinet at service entrance are to provided per the Line Diagram. It is unclear why this is so, considering the load side distribution equipment is existing. |
| 12/21/2004 | LLESNY1 | WWM | REVIEW | Needs Review | |
| 12/21/2004 | LLESNY1 | ENGINEERING | REVIEW | Needs Review |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 12/21/2004 | LISA LESNY | OUT TO CUSTOMER | Completed |