01/25/2005 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T04CM05455 DENIED 1/25/05
1. According to the Mechanical Plans, and the Mechanical Plans Examiner, both AC-4 and ER-1 are on the plans. Electrical Plans and Panel Schedule only account for AC unit but not ER. And the MCA for the AC unit on the plans is indicated at 15.4 MCA, which is correct for the ER. But the AC unit is 25.6 MCA. AC is 3-phase on Mechanical, but single phase on panel schedule.

Please include previously approved plans with next submittal.