Permit Number: T04CM05455
Parcel: 10321671B

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T04CM05455
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/05/2005 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved
01/05/2005 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied The pick up and storage for a dry cleaner store
is not classified as retail space per Table 403.3,
IMC 2000. Revise the ventilation calculations
to comply with Section 403.3, IMC 2000.
01/05/2005 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
01/25/2005 TACHONG1 WWM REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
01/25/2005 TAMI ACHONG OUT TO CUSTOMER Completed