Permit Number: T04CM05455
Parcel: 10321671B

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T04CM05455
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/04/2005 LLESNY1 WWM REVIEW Needs Review
12/17/2004 JIM EGAN FIRE REVIEW Approved
12/17/2004 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied Clarify what plumbing is new for this address.
12/17/2004 RAUL PALMA BUILDING-COMMERCIAL REVIEW Approved
12/17/2004 ROBERT SHERRY WATER REVIEW Approved
12/17/2004 PETER MCLAUGHLIN ZONING REVIEW Approved
12/17/2004 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Clarify what mechaical work is new for this address.
2. The pick up and storage for a dry cleaner store is not classified as retail space per Table 403.3, IMC 2000. Revise the ventilation calculations to comply.
12/17/2004 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T04CM05455 DENIED 12/17/04
1. IECC calculations use 3.3 W/SF for Retail Sales. Is 2.1 per Table 850.4.2.
2. IECC calculations use 0.9 W/SF for Storage. Is 1.0 per Table 850.4.2.
3. Tenant portion is smaller than storage in EICC calculations. On plans tenant portion is larger. Please clarify.
4. Line diagram lists Space F as existing, with load taken from separate engineering plans. Load Tabulations count 0 amps.
12/17/2004 PATRICIA GILBERT ENGINEERING REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
01/04/2005 LISA LESNY OUT TO CUSTOMER Completed