Review Details: COMMERCIAL TI
Permit Number - T04CM05430
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 12/16/2004 | JIM EGAN | FIRE | REVIEW | Approved | |
| 12/16/2004 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | Show that the existing 1/2" CW line is adequate to supply both the water closet and the lavatory. |
| 12/16/2004 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Show that the ventilation for the space conforms to Section 403.3, IMC 2000. |
| 12/16/2004 | CHRISTY FOREMAN | BUILDING-COMMERCIAL | REVIEW | Denied | 1) PROVIDE WATER CLOSET CLEARANCE PER ANSI A117.1 2) WALL SECTION FOR NEW WALLS. |
| 12/16/2004 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 12/30/2004 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Approved | T04CM05430 DENIED 12/17/04 1. Provide cut sheets for lighting fixtures. 2. Both meters and disconnects are marked "N". Panel schedules provided for panels A and N. Please clarify. 3. Match circuit nomenclature on plans with panel designations on panel schedules, typical. 4. Provide electrical requirements for new exhaust fan. Add to load on panel. 5. Provide a disconnect for the WH per NEC 422 Part III. 6. Account for continuous loading and largest motor on panel feeder calculations. |
| 12/30/2004 | GERRY KOZIOL | WWM | REVIEW | Approved | |
| 12/30/2004 | PATRICIA GEHLEN | ZONING | REVIEW | Approved | |
| 12/30/2004 | BLANCA ESPINO | ENGINEERING | REVIEW | Approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 12/30/2004 | TAMI ACHONG | OUT TO CUSTOMER | Completed |