Permit Number: T04CM05430
Parcel: 126070100

Address:
3920 E 5TH ST

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T04CM05430
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
12/16/2004 JIM EGAN FIRE REVIEW Approved
12/16/2004 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied Show that the existing 1/2" CW line is adequate to supply both the water closet and the lavatory.
12/16/2004 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Show that the ventilation for the space conforms to Section 403.3, IMC 2000.
12/16/2004 CHRISTY FOREMAN BUILDING-COMMERCIAL REVIEW Denied 1) PROVIDE WATER CLOSET CLEARANCE PER ANSI A117.1
2) WALL SECTION FOR NEW WALLS.
12/16/2004 ROBERT SHERRY WATER REVIEW Approved
12/30/2004 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved T04CM05430 DENIED 12/17/04
1. Provide cut sheets for lighting fixtures.
2. Both meters and disconnects are marked "N". Panel schedules provided for panels A and N. Please clarify.
3. Match circuit nomenclature on plans with panel designations on panel schedules, typical.
4. Provide electrical requirements for new exhaust fan. Add to load on panel.
5. Provide a disconnect for the WH per NEC 422 Part III.
6. Account for continuous loading and largest motor on panel feeder calculations.
12/30/2004 GERRY KOZIOL WWM REVIEW Approved
12/30/2004 PATRICIA GEHLEN ZONING REVIEW Approved
12/30/2004 BLANCA ESPINO ENGINEERING REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
12/30/2004 TAMI ACHONG OUT TO CUSTOMER Completed