Permit Review Detail
Review Status: Completed
Review Details: OTHER
Permit Number - T04CM05428
Review Name: OTHER
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 12/16/2004 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 12/16/2004 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Provide listing for the grease interceptor that shows a 2" outlet. Reference Sections 301.1.1 and 316.4.1, UPC 1994. 2. Provide one compartment of the 3-compartment sink with indirect waste. Refernce Section 801.2, UPC 1994. 3. Show that the location of the flow control device to conforms to Section 1011.3, UPC 1994. 4. Show that adequate access has been provided to the cleanout for the grease trap. reference Section 707.10, UPC 1994. |
| 12/16/2004 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Show how the hood is to be supported from the structure. Reference Section 507.6, IMC 2000. 2. Show that exhaust fan EF-1 has adequate access and service space. Reference Section 304.1, IMC 2000. |
| 12/16/2004 | CHRISTY FOREMAN | BUILDING-COMMERCIAL | REVIEW | Denied | 1) PROVIDE STRUCTURAL CALCS AND DETAILS FOR MOUNTING OF NEW HOOD. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 01/20/2005 | LISA LESNY | OUT TO CUSTOMER | Completed |