Permit Number: T04CM05428
Parcel: 13815012A

Address:
45 W VALENCIA RD

Review Status: Completed

Review Details: OTHER

Permit Number - T04CM05428
Review Name: OTHER
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
12/16/2004 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved
12/16/2004 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Provide listing for the grease interceptor that shows a 2" outlet. Reference Sections 301.1.1 and 316.4.1, UPC 1994.
2. Provide one compartment of the 3-compartment sink with indirect waste. Refernce Section 801.2, UPC 1994.
3. Show that the location of the flow control device to conforms to Section 1011.3, UPC 1994.
4. Show that adequate access has been provided to the cleanout for the grease trap. reference Section 707.10, UPC 1994.
12/16/2004 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Show how the hood is to be supported from the structure. Reference Section 507.6, IMC 2000.
2. Show that exhaust fan EF-1 has adequate access and service space. Reference Section 304.1, IMC 2000.
12/16/2004 CHRISTY FOREMAN BUILDING-COMMERCIAL REVIEW Denied 1) PROVIDE STRUCTURAL CALCS AND DETAILS FOR MOUNTING OF NEW HOOD.

Final Status

Task End Date Reviewer's Name Type of Review Description
01/20/2005 LISA LESNY OUT TO CUSTOMER Completed