Permit Number: T04CM05424
Parcel: 116270060

Review Status: Completed

Review Details: RESUBMITTAL - SITE

Permit Number - T04CM05424
Review Name: RESUBMITTAL - SITE
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/27/2005 JIM EGAN FIRE REVIEW Denied 1. Fire hydrant required. Submit approved City of Tucson Water Plan.
2. Type 1 exhaust hood and fire suppression system required for Kitchen Range.
3. Remove "Fire Sprinkler System" note from "Project Data"
The fire department does not make final determination for requirements. Requirements are determined by the Building Code, Architect and Building Owner.
07/25/2005 DOUG WILLIAMS ENGINEERING REVIEW Approved
07/27/2005 PETER MCLAUGHLIN ZONING REVIEW Denied 1. The 24-foot PAAL depicted on the drawing on sheet C1.1 passes through five vehicle parking spaces. PAALs may not run through parking spaces. The minimum required PAAL width for two-way traffic is 24 feet. PAAL and entrance drive at its narrowest points. There does not appear to be 24 feet provided at the southeast (entrance) to the parking lot. Revise drawing to show how parking lot will meet code.
DS 2-02.2.1.A.11
DS 3-05..2.1.C.1
LUC 3.3.7.2.A

2. Between any building and PAAL a minimum 5-foot pedestrian refuge area, including a 4-foot wide sidewalk, must be provided. Revise plan to show a pedestrian refuge with sidewalk near the south corner of the building between the PAAL and the building.

3. Correct the zoning (SR) of the adjacent property to the southwest of the site.

4. It is not clear where parking striping is proposed to be removed. Keynote 12 states that existing parking striping is to be removed, but the immediately adjacent keynote 8 indicates parking striping for stall deliniation. Clarify.

If you have any questions about this transmittal, please call Peter McLaughlin, (520) 791-5608.
08/03/2005 ANDREW CONNOR LANDSCAPE REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
09/21/2005 KMEDINA1 OUT TO CUSTOMER Completed