Review Date Reviewer's Name Type of Review Description Status Comments
06/27/2005 JIM EGAN FIRE REVIEW Denied 1. Fire hydrant required. Submit approved City of Tucson Water Plan.
2. Type 1 exhaust hood and fire suppression system required for Kitchen Range.
3. Remove "Fire Sprinkler System" note from "Project Data"
The fire department does not make final determination for requirements. Requirements are determined by the Building Code, Architect and Building Owner.
06/29/2005 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Second request. The minimum circuit ampacity and the maximum circuit protection for the units do not meet the manufacturer's requirements. Coordinate the electrical requirements for the HVAC units with the electrical design.
2. Second request. Provide a complete design for the Type I hood (i.e. mechanical, electrical, and structural). Reference Section 507.2.2 IMC 2000.
06/29/2005 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Note 2.22 on sheet A2.1 calls out a grill next to the range. Is it gas-fired, electric, or solid-fueled? Coordinate the plumbing plan with the architectural plan to include all existing and new plumbing fixtures. Reference Section 103.2.3, UPC 1994.
2. Provide fixture descriptions for all plumbing fixtures on the drawing. Reference Section 103.2.3, UPC 1994.
3. Sheet C1.1 shows the route and size of the water line from the clubhouse to the ramada but does not show the route of the water supply line to the clubhouse from the water meter on the drawing. Reference Section 103.2.3, UPC 1994.
4. Include all fixtures and directly connected appliances when calculating the total water demand and determining pipe sizes. Refer to keynotes #1 and #11 on sheet P1. Count the fixtures (e.g. hose bibbs, floor drains) shown on the plumbing floor plan on sheet P1. Use "public" values for fixture units. Reference Section 610.1, UPC 1994. See the Commercial Plan Review Submittal Requirements for the City of Tucson on http://www.tucsonaz.gov/dsd/. Provide water supply isometrics. (Note: All plans require a minimum 10pt font.) Reference Section 103.2.3, UPC 1994.
5. The equipment sheets for the ice maker do not indicate if it has integral backflow preventers or integral air gaps. Provide backflow protection per Section 603.0, UPC 1994.
6. Exception #4 to Section 707.4 is not applicable in this case. (Note also that exception # 4 to Section 707.4 refers to an "approved type of two-way cleanout fitting"; a field-fabricated two-way cleanout constructed with combination wye fittings is in violation of Section 707.6, UPC 1994.) Provide an upper terminal cleanout for the last water closet in the women's restroom. Reference Sections 707.4 and 707.5, UPC 1994.
07/05/2005 BOB SUBA ELECTRICAL-COMMERCIAL REVIEW Approved
07/25/2005 DOUG WILLIAMS ENGINEERING REVIEW Approved
07/25/2005 RAUL PALMA BUILDING-COMMERCIAL REVIEW Denied City of Tucson, Development Services
BUILDING AND STRUCTURAL COMMENTS

1) Where does detail 6/S3.2 apply?
2) How is the shear being transferred in detail 9/S3.2? Show all nailing, from
the diaphragm to the beam and down to the column and footing.
3) Compute the diaphragm nailing in calc`s.
4) Specify the zip code in calc`s.
5) On sheet 31 you specify STAAD OUTPUT where is this on calc`s?
6) Provide connection detail of handrail.
7) Provide panic hardware at all exit doors.
8) Provide exit signs at exit doors.
9) Provide exhaust hood connection details.


7/25/05

1) Refer to comment no. 1 above, cross-reference to where detail has been cut.
2) Refer to comment no. 2 above, comment is asking for all nailing.
3) Provide exhaust hood connection details.
07/27/2005 PETER MCLAUGHLIN ZONING REVIEW Denied Approved site plan required.