Permit Number: T04CM05424
Parcel: 116270060

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T04CM05424
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/19/2006 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. The details on sheet A4.2 appear to show combustible shelves within 18" of the hood in violation of section 507.9, IMC 2000.
2. Provide information to show that the top of the hood shown on sheet A4.2 has adequate clearance to combustibles (i.e. the ceiling / roof assembly), as well as adequate separation from the cooking surface. Reference Sections 308, 507.9, 507.10, and 507.11, IMC 2000.
3. Remove the note on the hood section (sheet A4.2) that offers wood studs with two layers of Type X sheetrock as an alternate wall construction. Reference Section 507.9, IMC 2000.
01/19/2006 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
01/25/2006 RAUL PALMA BUILDING-COMMERCIAL REVIEW Approv-Cond
01/27/2006 BOB SUBA ELECTRICAL-COMMERCIAL REVIEW Approved
02/03/2006 PETER MCLAUGHLIN ZONING REVIEW Denied Site plan approval required prior to bldg. approval.

Final Status

Task End Date Reviewer's Name Type of Review Description
02/10/2006 AOLIVO1 OUT TO CUSTOMER Completed
02/10/2006 SUE REEVES REJECT SHELF Completed