Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T04CM05424
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/19/2006 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. The details on sheet A4.2 appear to show combustible shelves within 18" of the hood in violation of section 507.9, IMC 2000. 2. Provide information to show that the top of the hood shown on sheet A4.2 has adequate clearance to combustibles (i.e. the ceiling / roof assembly), as well as adequate separation from the cooking surface. Reference Sections 308, 507.9, 507.10, and 507.11, IMC 2000. 3. Remove the note on the hood section (sheet A4.2) that offers wood studs with two layers of Type X sheetrock as an alternate wall construction. Reference Section 507.9, IMC 2000. |
| 01/19/2006 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Approved | |
| 01/25/2006 | RAUL PALMA | BUILDING-COMMERCIAL | REVIEW | Approv-Cond | |
| 01/27/2006 | BOB SUBA | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 02/03/2006 | PETER MCLAUGHLIN | ZONING | REVIEW | Denied | Site plan approval required prior to bldg. approval. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 02/10/2006 | AOLIVO1 | OUT TO CUSTOMER | Completed |
| 02/10/2006 | SUE REEVES | REJECT SHELF | Completed |