Permit Number: T04CM05420
Parcel: 127023460

Review Status: Completed

Review Details: POST 3RD PARTY REVIEW

Permit Number - T04CM05420
Review Name: POST 3RD PARTY REVIEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/04/2005 JIM EGAN FIRE REVIEW Approved 1. Fire sprinklers required per 2003 IBC and IFC Sec. 903.2.1.2 as amended. Provide complete fire sprinkler system design criteria on plan.
2. Manual fire alarm system required.
3. An approved fire apparatus turnaround is required for dead-end fire access roadways.
4. Indicate emergency ingress device (lock box) provided at gate.
02/10/2005 ROBERT SHERRY WATER REVIEW Approved
02/10/2005 GERRY KOZIOL WWM REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
02/23/2005 BETH GRANT OUT TO CUSTOMER Completed