Permit Number: T04CM05409
Parcel: 12213081A

Address:
3959 E MABEL ST

Review Status: Completed

Review Details: COMMERCIAL-BLDG/FIRE ONLY

Permit Number - T04CM05409
Review Name: COMMERCIAL-BLDG/FIRE ONLY
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/21/2005 Christy Foreman BUILDING-COMMERCIAL REVIEW Denied CITY OF TUCSON DEVELOPMENT SERVICES
STRUCTURAL REVIEW COMMENTS

DATE: 1/24/05
ACTIVITY NUMBER: T04CM05409
PROJECT NAME: Marion McDaniel Masonic Lodge #56
PROJECT ADDRESS: 3959 E. Mabel St.
ARCHITECT / ENGINEER: Keith Zwickl
PROJECT REVIEWER: Christy Foreman



TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL.

PLEASE CALL AT 791-5550 X1108 OR EMAIL AT CFOREMA1@CI.TUCSON.AZ.US IF YOU CARE TO DISCUSS.

1) Provide weep holes per section 2104.1.8 and section 1405.3.2.
2) Clarify lintel dimension see section 2104.1.5 and 1405.3.

Final Status

Task End Date Reviewer's Name Type of Review Description
01/24/2005 DELMA ROBEY OUT TO CUSTOMER Completed