Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL-BLDG/FIRE ONLY
Permit Number - T04CM05409
Review Name: COMMERCIAL-BLDG/FIRE ONLY
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/21/2005 | Christy Foreman | BUILDING-COMMERCIAL | REVIEW | Denied | CITY OF TUCSON DEVELOPMENT SERVICES STRUCTURAL REVIEW COMMENTS DATE: 1/24/05 ACTIVITY NUMBER: T04CM05409 PROJECT NAME: Marion McDaniel Masonic Lodge #56 PROJECT ADDRESS: 3959 E. Mabel St. ARCHITECT / ENGINEER: Keith Zwickl PROJECT REVIEWER: Christy Foreman TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL. PLEASE CALL AT 791-5550 X1108 OR EMAIL AT CFOREMA1@CI.TUCSON.AZ.US IF YOU CARE TO DISCUSS. 1) Provide weep holes per section 2104.1.8 and section 1405.3.2. 2) Clarify lintel dimension see section 2104.1.5 and 1405.3. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 01/24/2005 | DELMA ROBEY | OUT TO CUSTOMER | Completed |