Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T04CM05407
Parcel: 140292080

Review Status: Completed

Review Details: PLANS OK TO SUBMIT - 3RD PARTY

Permit Number - T04CM05407
Review Name: PLANS OK TO SUBMIT - 3RD PARTY
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
12/15/2004 JIM EGAN FIRE REVIEW Approved
12/15/2004 BLANCA ESPINO ENGINEERING REVIEW Approved
12/16/2004 MICHAEL ST. PAUL ZONING REVIEW Approved
12/16/2004 CHRISTY FOREMAN BUILDING-COMMERCIAL REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
12/16/2004 TAMI ACHONG OUT TO CUSTOMER Completed