Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T04CM05405
Parcel: 13338005E

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T04CM05405
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/03/2005 Robert Suba ELECTRICAL-COMMERCIAL REVIEW Denied 1.Min, font size is 10 pt. 2. Provide IECC calculations.
01/20/2005 Christy Foreman BUILDING-COMMERCIAL REVIEW Approved 1) According to records of shell permit the demising wall and restrooms are not where they are shown on Sht. A1. Clarify demising walls and both restrooms are new construction or provide city approved record drawings for the demising wall and restroom locations.
2) Area calculations appear to be inaccurate. See shell permit documents.
12/29/2004 Robert Sherry PLUMBING-COMMERCIAL REVIEW Denied 1. Comment not addressed. Provide riser diagram for the water supply to the restroom.
2. Comment not addressed. Revise the water pipe sizes to coordinate with the provided calculations.
12/29/2004 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Comment not addressed. Provide calculations to support the amount of outside air being provided to the space. Reference
Section 403.3, IMC 2000.

Final Status

Task End Date Reviewer's Name Type of Review Description
01/28/2005 DELMA ROBEY OUT TO CUSTOMER Completed